This site is 100% ad supported. Please add an exception to adblock for this site.

LFM Vol 3

Terms

undefined, object
copy deck
how often must exoansion loops be installed in alumimum pipline?
At least every 1000 feet of pipeline
Fuel flow is initally established throughout the fuel scavenging unit system when the
Deadman switch is acivated
How are the portable fuel transfer unit and FSU shut down in an emergency?
By activating their respective emergency buttons
When you install the portable fuel transfer unit separator, how many foot-pounds should you tighten the separator hex nuts?
10 ft-lbs
When you install the PFTU separtoe, how many foot-pounds should you tighten the coalescer hex nut?
10 ft-lbs
What is the first component you should check when the PFTU engine is hard to start?
Battery
How should the dike capacity compare to the bladdar capacity? the dike capacity should be
1 1/2 times the bladdar capacity
How much clearance must be maintaned between the bladdar and the dike wall?
2 feet
What must be the max distance from the dikes the aircraft's fuel receiving adapter?
250 feet
What is the minimum distance "jerry" cans and other flammable storage containers should should be stored from open flames or ignition source?
50 feet
what are the three types of fuel facilities used on any base?
Bulk, operating storage, and dispensing
What is the capacity of the R-22 pump?
900 GPM
How many R-14 fuel servicing modules does each air teansportable hydrant refueling system (ATHRS) contain?
3
What is the size of the Army's IPDS aluminum?
6" by 19'
At what fuel temp will the two stage tem switch shut down the portable fuel transfer unit (PFTU) diesel engine?
180 Degrees F
How many emergency stop switches are on the portable fuel transers unit (PFTU)?
2
How long should you idle the Portable fuel transfer unit to allow warm up?
2 mins
How long should idle the fuel scavenging unit (FSU) to allow warm-up?
2 mins
What is the minumum distance the portable fuel transfer unit should be places from the fuel source?
50 feet
What is the max distance that the fuel scavenging unit (FSU) should be placed from the pumping site?
140 Feet
What can you place on the bypass pit hose assembly to reduce the load on the coupling?
90-degree elbow
When making a bypass repair, on which side of the crater should you make the first cut?
On the pipe end closest to the crater
If residual fuel cannot be frained by other means, what equipment can you use to drain it?
Tapping and fuel suction equipment
What is the largest diameter hole that can be repaired in an 8-inch pipe?
Less than 4 inches
What is the MOST serious hazard associated with the contingency fuel recovery system (CFRS)?
Jet fuel Vapors
At what oxygen level are supplied-air resoirators required?
Below 19.5%
how many memebers are on the in-crater repair team?
3
What is the minimem distance between pipe cuts for the tyoe if repair that requires two hard wall hoses?
15 feet
What is the max allowable tow speed for the POL RIRK trailer on paved surfaces?
45 MPH
How long wil it take three POOL RUCK team members to repair an in-crater (bypass) 6" pipeline?
1 hour and 45 mins
What items critical for support of the POL RIRK are not included in the kit?
Fire extinguisher, tow vehicle, and backhoe
What can you use to complete the pipe cut if the pneumatic hacksaw fails?
Bow saw
Who should initally approach and circle the crater on foot with the automatic gas alarm?
Team chief
When you do an in-crater repair, what is the minimum amount of undamaged and cisibly round pip you should expose on each side of the damaged pipe section?
3 feet
What type respirator must be used for inert tank entry?
Type C
What is the preferred method of abandoning a 50,000 gallon tank?
Removal
What must be done to fuel pumps and motors located in a pit if they are to be abandoned?
Removed and stored in a dry place
Who directs the disposal of the fuel-water-sludge mixture contained in drums during tank cleaning?
BCE environmental coordinator
During tank cleaning, how often must you record vapor readings?
15 min intervals
During tank cleaning, where must an air compressor be positioned?
Upwind, just outside the dike
Artifical lights, other than battery-powered safety lanterns, can be used only during tank cleaning after what conditions is met?
The tank if vapor free
How much time from low battery alarm until the Bacharach 514 shuts down?
2 mins
What is the minimum voltage desired for the Bacharach 514?
5.2 Volts
If you suspect an unknown gas, which setting on the Bacharach 514 should you select?
Jp-5
Lifelines ised in tank cleaning have a service life of how namy years after their first use?
5
Positive mechanical ventilation should be provided for below grade pits that are how deep?
7 feet
During tank cleaning, when should you remove heavily contaminated clothing?
Immediately, but drench your self with water first
A safety Harness, used in tank cleaning, is good for a maz of how many years from the date stamped on the metal tag located on the back of the harness?
10 years
What type boot should you wear when entering a tank with 7 inches of fuel still in the tank?
3/4 length
People entering a fuel tank must wear what type of respirator?
Type C
All electrical equipment to be used within 50 feet of any fuel system must be defined as what class in the national electrical Code?
Class I, Division I, Group D
Which of the following fuels normally contains a higher concentration of benzene?
Gasoline
Who is responsible for inspecting a contractor's equipment before cleaning an Air Force Fuel tank?
LFM tank entry supervisor
To qualify for an Air Force tank cleaning contract, a contractor must provide proof of having completed similar work on how many previous projects?
Atleast 3
Who will assign a qualified tank entry supervisor to surevise a tank cleaning operation?
MAJCOM fuels engineer
Who is responsible for removing fuel from the tank to the lowest point possiblethrough existing connections?
Fuels management office
What prevents fuel from entering a roof drain line?
Flange gaskets and asbestos ring packing
In extremely cold climates, what should you do to the roof drain line?
Fill it with antifreeze
When you are inspecting the fabric seal on floating-roof tanks, what would indicate a warped sealing ring?
A gap between the metallic sealing ring and tank shell of 10 to 15 feet long
What is installed on a floating roof tank to help prevent out-of-roundness?
A wind girder
How is the product identification displayed on an aboveground tank?
Yelow bands with white letter on a black background
How many bands are used to identify JP-8 fuel?
Three
A pressure relief valve installed around the inlet block valve of a floating roof tank is adjusted to openat what pressure?
10 percent about system deadhead pressure
what is the inspection frequency for the thermal pressure relief valve?
Annually
During freezing weather, what is the inspection frequency of pressure/vacuum vents?
Daily
When must an internally coated diesel fuel tank be cleaned?
By direction of the fuels management office
At what point is uneven settling first considered dangerous for a floating roof tank?
5 inches
how often must you clean an internally coated bulk storage tank that receives fuel directly from a barge?
atleast every 5 years
How often must you clean an operating tank that is not internally coated and doesnt have a receiving filter separator?
At least every 3 years
How often must you clean out a bulk storage tanl that has receiving filter separator within one mile of its location and is internally coated?
at least every 8 years
At what level is an underground fuel tank is the low-level shut-off set to deenergize the fueling pump?
13 inches
The 129Af ball float is set to close the main valve when fuel in the underground tank reaches what level?
11 inches
What size is the clean out line on an underground tank and where does it terminate?
3/4 inches, 12 inches about ground level
The double-deck floating roof tank is the most efficient type of roof becuase the roof
has insulating air space between decks
How is the deck on a pontoon floating roof tank constructed?
The entire deck is a single thickness
What underground tank component prevents overfilling?
High-level shutoff valve
How many vents are installed on an all-weather tank?
3
The wind girder is installed on floating roof tanks to
Prevent the collapse of the tank shell
The roof guide is installed on floating roof tanks to
Keep the roof from rotating
What size is the water draw-off line in an all weather tank, and where does it terminate?
3/4 inch, 1/2 inch from the sump bottom
At what level does the high-level alarm actuate on a cone roof with floating pan?
Just before the high level shut-off valve
What is the size pipe used as the gauge well on a cone rook tank with floating pan?
8 inches
How and where does the product with drawel line terminate inside a cone roof tank with floating pan?
In a vertical position, 6 inches above the top of the sump
What is the slope of the stripping line inside an all-weather tank, and where does it terminate?
6 inches per 10 feet, 4 inches from the sump bottom
Who determines how many fuel tanks are required at each base?
The Defense Engery Support Center
What size water drawoff line is installed on a cone rook tank, and what is it piped to?
3/4 inch, 55 gallon product recovery system
In the confined-space entry program, at what height is hall protection required?
over 6 feet
In the confined-space entry program. how often must fall arrest equipment be inspected?
Before each use
Who among the confined-space rescue team must be familiar with toxic effect or symptoms of exposure to anticipated hazardous materials?
All entrants
Who noramally provides rescue service for operations requiring entry into permit-required confined spaces?
CE base Fire deparment
How often must organizational rescue team members receive hands-on resue training after initail training?
Annually
In the confined space entry program, who is responsible for making sure employees use PPE?
Supervisor
In the confined-space entry program, who develops a structured and effective training program to establish safe work practice and techniques?
Supervisor
In the confined-space entry program, who is the approval authority for the color of protective helmets?
Ground Safety
In the confined-space entry program, whom should you contact with questions concerning the hearing protection program?
Bioenvironmental Engineering
As a minimum, how often must a non-permit required confined space be reviewed to make sure conditions have not changed enough to create a poteneial for hazards and a need for a change in classification?
Annually
Who may reclassify a permit-required confined space to a non-permit confined space, at the time entry, if testing shows the space to be free of all hazards?
Entry Supervisor
Using the MEP as a guide, who may Authorize entry into the confined space by his or her signature on the entry permit?
Entry Supervisor
What AF form is used to authorize entry into a confined space?
AFForm 1024
Which of the following is not a function of the confined-space MEP?
Describe unacceptable entry conditions, under which permits may not be issued
Who is responsible for evaluating confined spaces for flammable, explosive, or oxygen-enriched atmosheres when permitting entries that are not covered by a MEP?
Fire Chief
Who must maintain all confined-space records?
Ground Safety
How are confined spaces classified?
By oxygen conten, flammablility, and toxicity
Which of the followind is not a member of the confined space program team?
Entry supervior
Which of the following conditions could cause a fluctuting flame in a preway heater?
Water in oil
Which of the following conditions could be the cause of high draft in a preway heater?
Additional lengths of stove pipe or high winds
You increase the heat output on a preway heater by turning the control knob
Counterclockwise
You clean the siphon assembly on a preway heater by flushing it with
Clean fuel oil
How many strokes are required to prime a preway heater?
4 to 6 stroked
When lighting a preway heater, you first press the reset lever of the fuelcontrol valve down and turn the control knob to
High Fire
Which burner is used in a preway tent heater?
Vaporizing pot burner
What is the minimum height above the highest point of the tent you install the smokestack on the preway tent heater?
18 inches
Which type of tent heater uses a siphon to start the fuel flowing from the fuel can to the control valve?
Preway
How do you repair a leaking plastic pipe joint in a waste system?
Replace the fitting
A pipe carrying steam is safety color-coded
Gray
A pipe carrying liquid oxygen is safety color-coded
Green
The back pressure regulators of the Harvest Eagle Water Distro are designed to keep a minimum system pressure of
20 PSI on the loop
How many evaporation neds are used in a field kitchen waste disposal system?
Seven
Hoe much potable water is produced by ROWPU if 1,200 gallons of water is pumped through the unit?
400 gallons Remember: 1200/3
The total pumping capacity of the Harvest Eagle raw water subsystem to the treatment site is
250 GPM
What is the most expansive subsystem of the Harvest Eagle water distribution system
Potable water
How much deflection does the hinged pipleine coupling allow for between joints?
2 percent
The total water storage of a Harvest eagle water distribution system is about
50,000 gallons

Deck Info

123

meo_failey

permalink