- how often must exoansion loops be installed in alumimum pipline?
- At least every 1000 feet of pipeline
- Fuel flow is initally established throughout the fuel scavenging unit system when the
- Deadman switch is acivated
- How are the portable fuel transfer unit and FSU shut down in an emergency?
- By activating their respective emergency buttons
- When you install the portable fuel transfer unit separator, how many foot-pounds should you tighten the separator hex nuts?
- 10 ft-lbs
- When you install the PFTU separtoe, how many foot-pounds should you tighten the coalescer hex nut?
- 10 ft-lbs
- What is the first component you should check when the PFTU engine is hard to start?
- Battery
- How should the dike capacity compare to the bladdar capacity? the dike capacity should be
- 1 1/2 times the bladdar capacity
- How much clearance must be maintaned between the bladdar and the dike wall?
- 2 feet
- What must be the max distance from the dikes the aircraft's fuel receiving adapter?
- 250 feet
- What is the minimum distance "jerry" cans and other flammable storage containers should should be stored from open flames or ignition source?
- 50 feet
- what are the three types of fuel facilities used on any base?
- Bulk, operating storage, and dispensing
- What is the capacity of the R-22 pump?
- 900 GPM
- How many R-14 fuel servicing modules does each air teansportable hydrant refueling system (ATHRS) contain?
- 3
- What is the size of the Army's IPDS aluminum?
- 6" by 19'
- At what fuel temp will the two stage tem switch shut down the portable fuel transfer unit (PFTU) diesel engine?
- 180 Degrees F
- How many emergency stop switches are on the portable fuel transers unit (PFTU)?
- 2
- How long should you idle the Portable fuel transfer unit to allow warm up?
- 2 mins
- How long should idle the fuel scavenging unit (FSU) to allow warm-up?
- 2 mins
- What is the minumum distance the portable fuel transfer unit should be places from the fuel source?
- 50 feet
- What is the max distance that the fuel scavenging unit (FSU) should be placed from the pumping site?
- 140 Feet
- What can you place on the bypass pit hose assembly to reduce the load on the coupling?
- 90-degree elbow
- When making a bypass repair, on which side of the crater should you make the first cut?
- On the pipe end closest to the crater
- If residual fuel cannot be frained by other means, what equipment can you use to drain it?
- Tapping and fuel suction equipment
- What is the largest diameter hole that can be repaired in an 8-inch pipe?
- Less than 4 inches
- What is the MOST serious hazard associated with the contingency fuel recovery system (CFRS)?
- Jet fuel Vapors
- At what oxygen level are supplied-air resoirators required?
- Below 19.5%
- how many memebers are on the in-crater repair team?
- 3
- What is the minimem distance between pipe cuts for the tyoe if repair that requires two hard wall hoses?
- 15 feet
- What is the max allowable tow speed for the POL RIRK trailer on paved surfaces?
- 45 MPH
- How long wil it take three POOL RUCK team members to repair an in-crater (bypass) 6" pipeline?
- 1 hour and 45 mins
- What items critical for support of the POL RIRK are not included in the kit?
- Fire extinguisher, tow vehicle, and backhoe
- What can you use to complete the pipe cut if the pneumatic hacksaw fails?
- Bow saw
- Who should initally approach and circle the crater on foot with the automatic gas alarm?
- Team chief
- When you do an in-crater repair, what is the minimum amount of undamaged and cisibly round pip you should expose on each side of the damaged pipe section?
- 3 feet
- What type respirator must be used for inert tank entry?
- Type C
- What is the preferred method of abandoning a 50,000 gallon tank?
- Removal
- What must be done to fuel pumps and motors located in a pit if they are to be abandoned?
- Removed and stored in a dry place
- Who directs the disposal of the fuel-water-sludge mixture contained in drums during tank cleaning?
- BCE environmental coordinator
- During tank cleaning, how often must you record vapor readings?
- 15 min intervals
- During tank cleaning, where must an air compressor be positioned?
- Upwind, just outside the dike
- Artifical lights, other than battery-powered safety lanterns, can be used only during tank cleaning after what conditions is met?
- The tank if vapor free
- How much time from low battery alarm until the Bacharach 514 shuts down?
- 2 mins
- What is the minimum voltage desired for the Bacharach 514?
- 5.2 Volts
- If you suspect an unknown gas, which setting on the Bacharach 514 should you select?
- Jp-5
- Lifelines ised in tank cleaning have a service life of how namy years after their first use?
- 5
- Positive mechanical ventilation should be provided for below grade pits that are how deep?
- 7 feet
- During tank cleaning, when should you remove heavily contaminated clothing?
- Immediately, but drench your self with water first
- A safety Harness, used in tank cleaning, is good for a maz of how many years from the date stamped on the metal tag located on the back of the harness?
- 10 years
- What type boot should you wear when entering a tank with 7 inches of fuel still in the tank?
- 3/4 length
- People entering a fuel tank must wear what type of respirator?
- Type C
- All electrical equipment to be used within 50 feet of any fuel system must be defined as what class in the national electrical Code?
- Class I, Division I, Group D
- Which of the following fuels normally contains a higher concentration of benzene?
- Gasoline
- Who is responsible for inspecting a contractor's equipment before cleaning an Air Force Fuel tank?
- LFM tank entry supervisor
- To qualify for an Air Force tank cleaning contract, a contractor must provide proof of having completed similar work on how many previous projects?
- Atleast 3
- Who will assign a qualified tank entry supervisor to surevise a tank cleaning operation?
- MAJCOM fuels engineer
- Who is responsible for removing fuel from the tank to the lowest point possiblethrough existing connections?
- Fuels management office
- What prevents fuel from entering a roof drain line?
- Flange gaskets and asbestos ring packing
- In extremely cold climates, what should you do to the roof drain line?
- Fill it with antifreeze
- When you are inspecting the fabric seal on floating-roof tanks, what would indicate a warped sealing ring?
- A gap between the metallic sealing ring and tank shell of 10 to 15 feet long
- What is installed on a floating roof tank to help prevent out-of-roundness?
- A wind girder
- How is the product identification displayed on an aboveground tank?
- Yelow bands with white letter on a black background
- How many bands are used to identify JP-8 fuel?
- Three
- A pressure relief valve installed around the inlet block valve of a floating roof tank is adjusted to openat what pressure?
- 10 percent about system deadhead pressure
- what is the inspection frequency for the thermal pressure relief valve?
- Annually
- During freezing weather, what is the inspection frequency of pressure/vacuum vents?
- Daily
- When must an internally coated diesel fuel tank be cleaned?
- By direction of the fuels management office
- At what point is uneven settling first considered dangerous for a floating roof tank?
- 5 inches
- how often must you clean an internally coated bulk storage tank that receives fuel directly from a barge?
- atleast every 5 years
- How often must you clean an operating tank that is not internally coated and doesnt have a receiving filter separator?
- At least every 3 years
- How often must you clean out a bulk storage tanl that has receiving filter separator within one mile of its location and is internally coated?
- at least every 8 years
- At what level is an underground fuel tank is the low-level shut-off set to deenergize the fueling pump?
- 13 inches
- The 129Af ball float is set to close the main valve when fuel in the underground tank reaches what level?
- 11 inches
- What size is the clean out line on an underground tank and where does it terminate?
- 3/4 inches, 12 inches about ground level
- The double-deck floating roof tank is the most efficient type of roof becuase the roof
- has insulating air space between decks
- How is the deck on a pontoon floating roof tank constructed?
- The entire deck is a single thickness
- What underground tank component prevents overfilling?
- High-level shutoff valve
- How many vents are installed on an all-weather tank?
- 3
- The wind girder is installed on floating roof tanks to
- Prevent the collapse of the tank shell
- The roof guide is installed on floating roof tanks to
- Keep the roof from rotating
- What size is the water draw-off line in an all weather tank, and where does it terminate?
- 3/4 inch, 1/2 inch from the sump bottom
- At what level does the high-level alarm actuate on a cone roof with floating pan?
- Just before the high level shut-off valve
- What is the size pipe used as the gauge well on a cone rook tank with floating pan?
- 8 inches
- How and where does the product with drawel line terminate inside a cone roof tank with floating pan?
- In a vertical position, 6 inches above the top of the sump
- What is the slope of the stripping line inside an all-weather tank, and where does it terminate?
- 6 inches per 10 feet, 4 inches from the sump bottom
- Who determines how many fuel tanks are required at each base?
- The Defense Engery Support Center
- What size water drawoff line is installed on a cone rook tank, and what is it piped to?
- 3/4 inch, 55 gallon product recovery system
- In the confined-space entry program, at what height is hall protection required?
- over 6 feet
- In the confined-space entry program. how often must fall arrest equipment be inspected?
- Before each use
- Who among the confined-space rescue team must be familiar with toxic effect or symptoms of exposure to anticipated hazardous materials?
- All entrants
- Who noramally provides rescue service for operations requiring entry into permit-required confined spaces?
- CE base Fire deparment
- How often must organizational rescue team members receive hands-on resue training after initail training?
- Annually
- In the confined space entry program, who is responsible for making sure employees use PPE?
- Supervisor
- In the confined-space entry program, who develops a structured and effective training program to establish safe work practice and techniques?
- Supervisor
- In the confined-space entry program, who is the approval authority for the color of protective helmets?
- Ground Safety
- In the confined-space entry program, whom should you contact with questions concerning the hearing protection program?
- Bioenvironmental Engineering
- As a minimum, how often must a non-permit required confined space be reviewed to make sure conditions have not changed enough to create a poteneial for hazards and a need for a change in classification?
- Annually
- Who may reclassify a permit-required confined space to a non-permit confined space, at the time entry, if testing shows the space to be free of all hazards?
- Entry Supervisor
- Using the MEP as a guide, who may Authorize entry into the confined space by his or her signature on the entry permit?
- Entry Supervisor
- What AF form is used to authorize entry into a confined space?
- AFForm 1024
- Which of the following is not a function of the confined-space MEP?
- Describe unacceptable entry conditions, under which permits may not be issued
- Who is responsible for evaluating confined spaces for flammable, explosive, or oxygen-enriched atmosheres when permitting entries that are not covered by a MEP?
- Fire Chief
- Who must maintain all confined-space records?
- Ground Safety
- How are confined spaces classified?
- By oxygen conten, flammablility, and toxicity
- Which of the followind is not a member of the confined space program team?
- Entry supervior
- Which of the following conditions could cause a fluctuting flame in a preway heater?
- Water in oil
- Which of the following conditions could be the cause of high draft in a preway heater?
- Additional lengths of stove pipe or high winds
- You increase the heat output on a preway heater by turning the control knob
- Counterclockwise
- You clean the siphon assembly on a preway heater by flushing it with
- Clean fuel oil
- How many strokes are required to prime a preway heater?
- 4 to 6 stroked
- When lighting a preway heater, you first press the reset lever of the fuelcontrol valve down and turn the control knob to
- High Fire
- Which burner is used in a preway tent heater?
- Vaporizing pot burner
- What is the minimum height above the highest point of the tent you install the smokestack on the preway tent heater?
- 18 inches
- Which type of tent heater uses a siphon to start the fuel flowing from the fuel can to the control valve?
- Preway
- How do you repair a leaking plastic pipe joint in a waste system?
- Replace the fitting
- A pipe carrying steam is safety color-coded
- Gray
- A pipe carrying liquid oxygen is safety color-coded
- Green
- The back pressure regulators of the Harvest Eagle Water Distro are designed to keep a minimum system pressure of
- 20 PSI on the loop
- How many evaporation neds are used in a field kitchen waste disposal system?
- Seven
- Hoe much potable water is produced by ROWPU if 1,200 gallons of water is pumped through the unit?
- 400 gallons Remember: 1200/3
- The total pumping capacity of the Harvest Eagle raw water subsystem to the treatment site is
- 250 GPM
- What is the most expansive subsystem of the Harvest Eagle water distribution system
- Potable water
- How much deflection does the hinged pipleine coupling allow for between joints?
- 2 percent
- The total water storage of a Harvest eagle water distribution system is about
- 50,000 gallons